WARNING:
TEST FOR LEAKS
A complete gas tightness check must be performed at
the installation site.
CAUTION:
To prevent fire or explosion hazard, DO NOT use or
permit sources of ignition in the area while performing
a leak test. Perform leak test outdoors only. Never
perform a leak test with fire or flame. DO NOT SMOKE
WHILE PERFORMING THE LEAK TEST.
• Use an approved non-corrosive leak detection
solution or create a soapy solution of equal parts mild
dishwashing detergent and water.
• Check to be sure all controls are in the OFF position.
• Turn on the fuel supply. For natural gas, turn manual
shut-off valve handle 1/4 turn to align with gas flow.
For LP, turn cylinder valve knob counterclockwise one
full rotation.
• Apply liquid leak detector generously on all
connections and fittings. See illustrations.
• If growing bubbles appear on any connection point,
IMMEDIATELY turn off the gas supply.
To stop a gas leak:
• Turn off the fuel supply.
• Turn on control knobs to release pressure. Turn
controls OFF.
• Wash off soapy solution and towel dry.
• Tighten the loose joint and perform a new leak test.
14
All manuals and user guides at all-guides.com
Installation
Natural Gas Leak
Test Points
LP Gas Leak
Test Points
31-11026