Descargar Imprimir esta página

Siemens SIMATIC ET 200SP HA/ET 200SP Información Del Producto página 12

Sistema de periferia descentralizada
Ocultar thumbs Ver también para SIMATIC ET 200SP HA/ET 200SP:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 21
Ex-AI 4xTC 2xRTD 2-3-4-wire
You must observe the guidelines according to DIN EN IEC 60079-17 for functional
checks.
Derating
The table shows the maximum permissible output current for the Ex-Power Module
depending on the installation position and the ambient temperature.
Mounting position
Horizontal installation
Vertical installation
Specific conditions of use
CAUTION
Specific conditions of use
1. This equipment shall be installed in an enclosure with an ingress protection of at
least IP54 in accordance with EN 60079-0 and EN 60529. The installation shall also
ensure Pollution Degree 2 (as defined in EN 60664-1) inside the enclosure. And all
circuits shall be limited to Overvoltage category I or II. These requirements apply
even when installed in a non-hazardous area.
2. The earth connection of the mounting rail shall be connected to the local
equipotential bonding system according to the applicable installation standard.
3. Transient protection shall be provided that is set at a level not exceeding 140 % of
the peak rated voltage value at all supply terminals to the equipment, or at most
set at 119 V.
Maintenance
The Ex-I/O modules are maintenance-free.
In general, pulling or plugging modules is not allowed in Zone 2. Before starting work,
make sure that there is no explosive atmosphere or that the power supply is switched
off.
For repairs, you must send the I/O module to the manufacturing location. The repair
may only be carried out there.
For use in the USA and Canada
The control drawing for the ET 200SP HA and the ET 200SP is supplied with the
respective power supply module.
The latest edition can also be found at
URL: (https://support.industry.siemens.com/cs/ww/en/)
12
Ambient temperature
From -40 °C to 60 °C
From -40 °C to 70 °C
From -40 °C to 50 °C
From -40 °C to 60 °C
Output current
0.8 A
0.6 A
0.8 A
0.6 A
Ex-AI 4xTC 2xRTD 2-3-4-wire
A5E50377623-AA, 04/2021

Publicidad

loading

Este manual también es adecuado para:

Ex-ai 4xtc 2xrtd 2-3-4-wire6dl1134-6jd00-0hx1