Please read all instructions before installing
SPECIFICATIONS
Voltage ........................................................................ 120VAC, 60Hz
Load (Multi-Way)
Incandescent or fluorescent ...................................... 0-600 Watts
Fan motor ............................................................................ 1/6 hp
Time Delay Adjustment .................... 15 sec., 5 min., 15 min., 30 min.
Light Level Adjustment ................................................. 10 fc to 150 fc
Environment ............................................................... Indoor use only
Operating Temperature ..........................32° to 131°F (0° to 55°C)
Humidity ................................................ 95% RH, non-condensing
Tools Needed
Insulated Screwdriver
Wire Strippers
DESCRIPTION AND OPERATION
RH-250 Multi-way Wall Switch Convertible Occupancy Sensors are designed
to replace standard single pole and multi-way (3-way, 4-way) switches. They
are ideal for any room with multiple entries and any other indoor space where
vacancy sensor-based controls with manual ON/OFF capability are desirable.
Like standard switches, you can press the ON/OFF button to turn the light or fan
(controlled load) ON and OFF. Unlike standard switches, the RH-250 automatically
turns OFF the controlled load after the coverage area has been vacant for a period
of time (Time Delay). If motion is detected within 30 seconds after it automatically
turns OFF, the RH-250 automatically turns the load back ON.
While the sensor is factory preset as a Vacancy Sensor with manual ON operation,
it can be adjusted to work as an occupancy sensor that turns the controlled load
ON automatically upon detection of occupancy in the area.
The RH-250 can be wired with up to three additional RH-250s for multi-way
Manual/Auto–ON/OFF of one or several loads (up to one load connected to each
RH-250). It can also be wired to up to four RH-253 single pole momentary wall
switches for multi-way Manual-ON/OFF Automatic-OFF control of one load.
Lighted Switch
To help you locate the RH-250 in a dark room, the amber LED illuminates the
ON/OFF button while the controlled load is OFF. When the controlled load is ON,
the LED is OFF.
Operating Modes
For multi-way operation of two or more RH-250s, we recommend that the
Operating Mode be the same in all sensors related to the same load. This
makes it easier to understand the multi-way control operation as well as trouble
shooting. There are two operating modes to select from:
MODE 1 Vacancy sensor (Manual-ON/OFF, Auto-OFF): The user must press
the ON/OFF button to turn the load ON. The RH-250 keeps the load ON until no
motion is detected by any of the related RH-250s for the time delay period. There
is also a 30 second reset delay after the automatic shut-off. If motion is detected
during this time, the sensor turns the load back ON automatically. After the 30
second reset delay has elapsed, the ON/OFF button must be pressed to turn ON
the load.
MODE 2 Occupancy sensor (Auto-ON/OFF with manual control and reset to auto
Call 800.879.8585 for Technical Support
Multi-Way Wall Switch
Occupancy Sensor
Santa Clara, CA 95050
RH-250
Convertible

Publicidad

loading

Resumen de contenidos para wattstopper RH-250

  • Página 1 MODE 1 Vacancy sensor (Manual-ON/OFF, Auto-OFF): The user must press the ON/OFF button to turn the load ON. The RH-250 keeps the load ON until no motion is detected by any of the related RH-250s for the time delay period. There is also a 30 second reset delay after the automatic shut-off.
  • Página 2 Pull the old switch out from the wall box. 2. Identify the type of circuit. You may connect the RH-250 to a single pole or multi-way circuit. If you are unable to clearly identify some or all of the wires mentioned in this manual, you should consult with a qualified electrician.
  • Página 3 “Strip Gage,” in Fig. 3. (approx. 1/2 inch). 4. Wire the sensor. Twist the existing wires together with the wire leads on the RH-250 sensor(s) as indicated in either step 4a or 4b. Cap wires securely using wire nuts. 4a. Wiring two RH-250s in a 3-way configuration • Connect the green or non-insulated (copper) GROUND wire from the circuit to...
  • Página 4 (4 maximum) 5. Put all the new switches into their wall boxes. Position the RH-250 switch(es) with the lens above the ON/OFF button (lens at top, ON/OFF button at bottom). Use the captive screws on the mounting strap to secure the switches to their wall boxes.
  • Página 5 ON automatically with occupancy if the light level measured at this sensor is above the current natural illumination. 5. Repeat the process (beginning with step 1) for each RH-250 in your multi-way configuration until the Light Level has been adjusted properly in all of them.
  • Página 6 4. Repeat as necessary to ensure that the desired coverage areas are within detection range. You can do this test for each RH-250 in your multi-way configuration. So that you can determine the actual coverage area for each multi-way switch individually, only the RH-250 that is in TEST mode will control the load.
  • Página 7 área de cobertura. El RH-250 puede ser conectado a un máximo de tres RH-250 adicionales para el control de encendido/apagado manual o automático de una o varias cargas (hasta una carga por cada RH-250) desde varios lugares.
  • Página 8 Extraiga el interruptor existente de la caja. 2. Identifique el tipo de circuito. Usted puede conectar el RH-250 a un circuito unipolar, o una conexión de 3 o 4 vías. Si usted es incapaz de identificar claramente alguno de los cables mencionados en este manual, usted debe consultar con un electricista calificado.
  • Página 9 RH-250. • Conecte el cable de conexión a NEUTRO del circuito y de la lámpara o ventilador (CARGA) al cable blanco del RH-250 denominado como “maestro”. Conecte un cable de conexión a neutro al cable blanco del otro RH-250 denominado como “auxiliar”. El término “maestro” es utilizado acá únicamente para designar el sensor que esta conectado directamente a la carga controlada.
  • Página 10 4b. Conexión de un RH-250 y un interruptor momentáneo unipolar RS-253 en una configuración tipo 3 vías para control manual de encendido/ apagado desde dos ubicaciones. IMPORTANTE: El RH-250 debe ser instalado en la caja de conexiones que conecta con la carga.
  • Página 11 5. Repita este proceso (empezando con el paso 1) para cada RH-250 en su cableado tipo 3 o 4 vías hasta que el Nivel de Luz Natural haya sido ajustado apropiadamente en cada uno de los sensores.
  • Página 12 Usted puede realizar esta prueba para cada uno de los RH-250s en su cableado tipo 3 o 4 vías. De tal forma que usted pueda corroborar adecuadamente el patrón de cada sensor individualmente, solo el RH-250 que esta en Modo de Prueba controlara la carga.