KGXD stacked air routing
(with external bypass)
Mount slide-in rail.
Reinsert mist eliminator.
For upper bypass damper (damper loosely supplied):
Secure the bypass damper with screws at the intended holes on the top and bottom
of the supports.
Slide the support back up and secure to
the cover and partition with screws.
Use props if available on site.
For top TA:
Mount condensate deflector (loosely
supplied) at top TA as follows during
execution.
Apply sealant along the edge of the
deflector to the cube element, press the
condensate deflector down, and seal
around the circumference.
Any condensate must drain off through the
fins in the plate element.