GB
3.5.5
Adapting the upstream fuse /transformer options
Only cooling units with the rated operating voltage 400V / 460V can be optionally connected to a different mains
voltage.
▪ Reconnection takes place via the supply of the primary side of the transformer.
The upstream fuse must match the changed mains voltage; see Adapting the upstream fuse.
Figure 16 - Transformer options
Transformer - Option
T1/ 1 [0] – T 1/ 2 [400]
400 V
T1/ 1 [0] – T 1/ 3 [440]
440 V
T1/ 1 [0] – T 1/ 4 [460]
460 V
3.5.6
Components for internal protection
•
Cooling units have several safety components.
2
Figure 17 – Components for internal protection
3.5.7
Collective fault signal
• Two connections are provided for connection of the collective fault signal. They are marked with the item
designation SK; see
• The fault signaling contact is potential-free.
Ensure that the contact is loaded with a maximum of 230V, 1 A.
Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014d © Pfannenberg GmbH
The specifications for the factory settings of the transformer are
provided on the yellow connection diagram (1) on the rear side of the
unit.
UL-conformity with the following fuses:
Category "ClassCC", slow-burning.
1
1
Electrical
connection.
Pre-fuse (Min. 480 V)
Functional equipotential-bonding M8 thread (1), for a
signal reception with low interference between the unit and
the switch cabinet.
Protective equipotential-bonding (2) for metal
components and touch voltage.
Max. 4 A
Max. 4 A
Max. 4 A
Page 25 / 43