14.5.
PARALLEL OPERATION FOR TWO OR MORE
ALTERNATORS
The reactive compensation method applied is called a phasor diagram (see Figure 14.5.1). Through this diagram, the
alternator output voltage signal is measured and compared with the alternator current voltage. The result of this interaction
introduces a sensing error of the actual voltage signal, causing an increase or a decrease in the alternator voltage, thus
maintaining the reactive between the alternators within acceptable values. The adjustment of this compensation is made
through trimpot Drp.
According to the phasor diagram, the sensing voltage is influenced by the current coming from phase S, which is added to
the voltage of phases R and T. The influence is small in module and large in phase, which means that there is good
compensation for reactive loads and a small influence with active loads.
The current transformer (CT) for reactive compensation must be in phase S of the alternator, and the voltage sensing
signal must be in phases R and T.
To make sure the compensation is in the proper direction, proceed as follows:
Operate the alternator by itself (isolated from the grid) and apply a resistive load with about 20% of the alternator capacity;
After completely rotating the Drp trimpot clock wise (CW), the alternator voltage should decrease.
Rotating back the trimpot completely CCW, alternator voltage should then increase; If this occurs, the CT polarity is correct.
Otherwise the CT should be inverted.
When several alternators are connected in parallel, this procedure is required to ensure that all the CT's are properly
polarized.
The current transformer for compensation of reactive must be in phase S of the alternator and the feeding signal in the
phase R.
To ensure the correct polarization of TC, Inductive Resistive loads must be applied and the system checked for good
response as below.
Resistive Loads: It will not present compensation with resistive load, keeping the excitation current and alternator voltage
constant in the value adjusted via trimpot Drp. In case of compensation, it indicates that TC is in the wrong phase.
Inductive Loads: With inductive load application, it shall present negative compensation, decreasing the excitation current
corresponding to the gain adjusted in the trimpot Drp (0 to 15% voltage adjusted in the Vad. If the compensation is positive,
it indicates the TC is inverted.
Capacitive Loads: With application of capacitive loads, it will present a positive compensation, increasing the excitation
current corresponding to the gain adjusted in the trimpot Drp (0 to 15% voltage adjusted in the Vad. If the compensation
is positive, it indicates the TC is inverted.
Accuracy class of 0,6C12,5;
Window or bar type;
Transformer ratio will be In/5A or In/1A, where In/xA is the ratio of the TC primary. Ex.: 100/5A, 150/5A, 100/1A;
5A secondary current for regulator PAR/5 and 1A for regulator PAR/1;
The current in TC primary must be 20% bigger than the nominal current of the machine;
The TC operation frequency must be equal to the alternator frequency;
The TC isolation voltage class must be bigger than the alternator output voltage;
It must support 1.2 x In.
R
Figure 14.5.1: Phasorial diagram
Automatic Voltage Regulator – AVR-A-OPT-07 / AVR-A-OPT-07E / AVR-A-OPT-07/T l 17