In case of an installation where cabling is outdoors, it must be installed inside a
cable ducting system with IP4X protection degree classified as "cable ducting with
access cover that can only be opened with a tool" according to UNE-EN 50.085-1:
Cable trunking systems and cabling ducting systems for electrical installations-
Part 1: General requirements.
START UP
Operating modes (see Fig.2)
MF1: Relay + Modbus (reading) – [SW1-3=OFF]
Adjustable relay via P1 potentiometer. Factory settings: 1200 ppm / 70%HR
MF2: 0-10Vdc output analogue signal + Modbus (reading) – [SW1=ON, SW2-3=OFF]
0-10Vdc output analogue signal adjustable via P1 potentiometer. Factory set-
tings: 1200 ppm / 70%HR
MF3: 2-10Vdc output analogue signal + Modbus (reading) – [SW1-2=ON, SW3=OFF]
2-10Vdc output analogue signal adjustable via P1 potentiometer. Factory set-
tings: 1200 ppm / 70%HR
MF4: Modbus control – [SW1-3=ON]
Access to reading, edition and communication of working parameters via Mod-
bus communication protocol (see Table 1, Modbus registers). Relay and output
analogue signal enabled. Factory settings: 1200 ppm / 70%HR
Note: If other switch combination is chosen, LED diffuser is switched off and
digital/ analogue signals are inoperative. Microswitches SW5-6 must remain OFF
for correct operation.
On electronic board there are three LEDs (see Fig.1) with the following functions.
LED
Colour
D17
Red
D16
Red
D18
Yellow
LED diffuser
The device displays a real-time concentration level. In operation mode 1, the illu-
mination is two-color while in modes 2, 3 and 4 this is three-color. Light intensity
is adjustable via P2 potentiometer (see Fig.1) from OFF to 100%.
Relay + Modbus (reading) – [SW1-3=OFF]
Green: Value below set point.
Red: Value above set point.
Description
On: Device powered
On: Modbus communication failure
On: When Modbus communication is established