diffuser in red. During this period it is necessary to keep the equipment powered
so as not to interrupt the self-calibration process.
Manual calibration AIRSENS CO2
For those situations where automatic calibration is an impediment, a forced
manual calibration can be performed. To do this, press the button (see Fig.1) for
more than 10 seconds until the light guide flashes intermittently in green. During
the next 10 minutes of flashing it is essential that there is no occupation in the
area, windows remain open and/or the ventilation system at maximum perfor-
mance in order to obtain the best CO
the light guide will stop flashing and the AIRSENS CO2 will consider that the CO
level in that moment is 450ppm.
Reset
Manual way to start a reset process is disconnecting power supply, wait at least
30 seconds and power again the electronic control. It is also possible to do re-
motely via Modbus communication using General reset (register number 3).
TECHNICAL DATA
Power supply voltage ........................... 100-240Vac – 50/60Hz
Protection against electric shock ........ Class II
Installation type required ..................... Tipo X
Maximum consumption ....................... 0,7W
Maximum current ................................ 0,01A
Output................................................... 0-10Vdc, 2-10Vdc, maximum current 20mA
Relay NC .............................................. 3A – 250Vac
Relay NO .............................................. 3A – 250Vac
Electric connection:
All cables used must fulfil with IEC 60.227.
5 x terminals, supply and relay ............ Min. 0,5 mm
5 x terminals, analogue output
and Modbus .......................................... Min. 0,25 mm
Note: Same tool can be used for both terminals types
Measurement range:
CO2 ....................................................... 450-2000ppm
VOC ....................................................... 450-2000ppm (CO2 equivalent relative)
RH......................................................... 45-100%
concentration possible. After 10 minutes,
2
cable / Máx. 1,5 mm² cable
2
M3 screw and 0,5 Nm torque
cable / Máx. 1,0 mm² cable
2
M2 screw and 0,3 Nm torque