The detailed status is shown as follows when the input voltage protection occurs:
Input voltage
protection
The output is switched OFF immediately.
The blue indicator flashes fast.
Over voltage
The buzzer beeps.
protection
The LCD display shows
Over voltage
The blue indicator is ON without flashing.
recovery
The output voltage is normal.
protection
The output is switched OFF immediately.
The blue indicator flashes slowly.
Low voltage
The buzzer beeps.
protection
The LCD display shows
Low voltage
The blue indicator is ON without flashing.
recovery
The output voltage is normal.
protection
3.
Note: While the inverter is equipped with input over-voltage protection, the surge voltage must
not exceed 20V for a 12V system, 40V for a 24V system, or 80V for a 48V system. Otherwise, the
inverter may be damaged.