Specifications
Model
UV2400U2000 AirBRIGHT 2
Size and Weight
Power Module: 4.75" L x 3.16" W x 1.75" H
Mounting Bracket (Magnetic): 3.5" L x 2.25" W x 3.5" H
Weight: 2 lbs.
Electrical
Power: 24VAC (Expanded range ballast: 20V-30V), 50/60Hz, 1.0A. 3000V surge protection.
Cordage: Two pre-crimped and pre-soldered wire leads; 3-ft 24V power input cable and
Ozone
UL 2998 validated no ozone.
Meets California ozone emissions limit: CARB certified.
Lamp
High-humidity, water-resistant, 15" lamp length.
Lamp Life
18,000 hour.
Construction
Injection-molded thermoplastic co-polymer high-strength power module.
Replacement Parts UV2400XLAM2 The initial bulb is a two year bulb but should be replaced every year after
that.
UV Installation Notes
We recommend the AirBRIGHT 2 UV Air Purifier be installed on the supply side duct 3-5 inches above
the A-coil, but it can also be installed on the return side if necessary.
The germicidal UV light should be positioned to shine on the surfaces that are prone to mold growth like
the A-coil, or be placed in an open area of the return duct where there are long straight runs.
Install the magnetic switch and add the included stickers bearing the ULTRAVIOLET RADIATION hazard
symbol on any doors/access panels which would allow direct UV light to shine through if opened while
UV is powered. Make sure any doors/panels without magnetic switch remain closed while the UV is
powered.
To comply with UL Standards, a magnetic switch must be deployed across all access panels and doors
that can expose an operator to more than of 1.7 μW/cm2 UV intensity.
Do not operate UV-C LAMPS outside of the appliance.
Wiring And Transformer Installation Notes
This device requires a constant 24 VAC power source. It is recommended that the device be powered by a
dedicated, non-cycling, 40VA transformer. Cycling this UV light will void the lamp's warranty and lessen the
effective lifetime of the lamp. If powering from an existing transformer already integrated on a furnace, air
handler, or other appliance, an upgrade may be required to the original equipment transformer. Ensure there is
adequate volt-ampere (VA) capacity on the existing transformer to support an additional 1.4A draw from this
product.
Verify the available volt amperes prior to connecting the UV fixture to the 24 VAC circuit. Energize all 24
1
VAC components so they reach their maximum amp load.
After obtaining the available volt amperes, determine if the existing transformer can accommodate a 1.4
2
amp load.
Beware that inadequate transformers may initially seem to power up the circuit only to then overheat as a
3
result of an overdrawing system.
After installing the UV fixture, energize all 24 VAC components at their full amp draw, including the UV
4
fixture, and ensure that all systems are operational and that fuses remain intact.