Descargar Imprimir esta página

ICS Schneider Messtechnik SwitchGauge PGS23 Manual De Instrucciones página 25

Publicidad

Idiomas disponibles

Idiomas disponibles

9. Specifications
Models PGS21.100, PGS21.160
Pressure limitation
- Steady
- Fluctuating
- Short time
Temperature effect
For further specifications see data sheet PV 22.01
Models PGS23.100, PGS23.160, PGS26.100, PGS26.160
Pressure limitation
- Steady
- Fluctuating
- Short time
Temperature effect
For further specifications see data sheet PV 22.02
Model PGS23.063
Pressure limitation
- Steady
- Fluctuating
- Short time
Temperature effect
For further specifications see data sheet PV 22.03
Models PGS43.100, PGS43.160
Pressure limitation
- Steady
- Fluctuating
- Short time
Temperature effect
For further specifications see data sheet PV 24.03
Operating instructions pressure gauges with switch contact models 821, 851 or 830 E
Full scale value
0.9 x full scale value
1.3 x full scale value
When the temperature of the measuring system deviates from the
reference temperature (+20 °C): max. ±0.4 %/10 K of full scale value
Full scale value
0.9 x full scale value
1.3 x full scale value
When the temperature of the measuring system deviates from the
reference temperature (+20 °C): max. ±0.4 %/10 K of full scale value
3/4 x full scale value
2/3 x full scale value
Full scale value
When the temperature of the measuring system deviates from the
reference temperature (+20 °C): max. ±0.4 %/10 K of full scale value
Full scale value
0.9 x full scale value
5 x full scale value, however max. 40 bar
When the temperature of the measuring system deviates from the
reference temperature (+20 °C): max. ±0.8 %/10 K of full scale value
EN
25

Publicidad

loading