Operating instructions
5
Assembly
5.1
Installation position
With regard to the installation position, pay attention to the arrow showing the flow direction. When installing
the globe valve in a horizontal pipeline, a vertical position of the stem is recommended (handwheel at the
top) or an inclination of up to 65° from the vertical.
5.2
Fitting Notice
Use suitable tools.
Allen key;
Open-ended spanners;
Torque wrench;
TIG welding machine;
Oxy-fuel welding machine;
Clean tools before fitting.
Use suitable transport and lifting equipment for installation.
Open the packaging immediately before installation. Free of oil and grease for oxygen (O2)
Valves for oxygen are permanently marked with "O2".
Take note of the HEROSE information sheet "O2 instructions".
Only install the globe valve if the maximum working pressure and operating conditions of the plant
correspond to the marking on the valve.
Remove protective caps or covers before mounting.
Check the valve for dirt and damage.
DO NOT install a damaged or dirty valve.
Avoid damaging the connections.
The sealing surfaces must remain clean and intact.
Seal the valve with suitable seals.
No sealant (sealing tape, liquid sealant) may enter the valves.
Respect the suitability for use with O2.
Connect pipelines in a force-free and torque-free manner.
Stress-free mounting.
In order to ensure trouble-free operation, no impermissible static, thermal or dynamic stresses may be
transmitted to the valve. Observe reaction forces.
Temperature-dependent changes in length in the pipework system must be compensated with expansion
joints.
The valve is supported by the pipework system.
Detailed installation instructions are included for globe valves with pneumatic or electric actuator-unit.
Driven valves: Mounting/dismantling the bonnet in the centre position of the actuator.
The valve must be protected against dirt and damage during construction work.
Remove any transport locks such as blocking bushing (optional).
Check the leak-tightness.