Problem
Mini fridge is not cooling. Interior light
is flashing continously.
Poor cooling performance
Frost formation in the mini fridge com-
partment
Possible cause
Flashing 3x: Heating cartridge is de-
fective (only for versions with absorber
cooling).
Flashing 5x: CPC (cooling perfor-
mance control) error.
For versions with absorber cool-
ing: Error during self-test of the cool-
ing unit.
Cooling unit is not sufficiently ventilat-
ed.
Mini fridge is exposed to direct sun-
light.
Door of mini fridge is not closed with
a tight seal.
Mini fridge recently filled.
For versions with absorber cool-
ing: The input voltage is too low or
too high.
Auto-defrost function is active.
Door of mini fridge is not closed with
a tight seal.
Dometic Hipro Care EN
Suggested remedy
Contact an authorized service
agent.
Service agent only: Install a
new heating cartridge.
1.
Temporarily disconnect the mini
fridge from the power supply to
reset the error.
2.
Count the number of flashes that
occur after the reset:
• Flashing 1x: NTC sensor is defec-
tive.
• Flashing 3x: Heating cartridge is
defective (only for versions with
absorber cooling).
• No flashing: Error is reset.
3.
Flashing 1x or 3x: Contact an au-
thorized service agent.
Note: After a longer period of
time without troubleshooting,
the LED changes back to the in-
terval of flashing 5x.
Check the cooling unit for leaks.
Check the ventilation grille of the
cooling unit and ensure optimal
performance.
Wait 24 h for the device to
restart cooling. If the device
does not restart within 24 h, con-
tact an authorized service agent.
Provide sufficient ventilation (see Instal-
lation Manual).
Remove the mini fridge out of direct
sunlight.
Check distances (see Installation Man-
ual).
Contact an authorized service
agent.
Service agent only: Replace
door seal
Check cooling again after 5 h ... 6 h.
Check input voltage.
No action required (see chapter
frosting
on page 13).
Check distances (see Installation Man-
ual).
De