2.10.Measure soil resistivity.
2.11.Pylon measurement function(
2.7. With RS232 and USB interface
*PS.: RS232 and USB interface only for secondary development or improvement, can supply the Serial
Protocol, not provide the background software.
3. Technical breakthrough
3.1.Step voltage option can setting the current output time control, can set the constant current
output time as reqeust.
3.2.Storage uses keyboard input to convient query.
3.3.After step voltage testing, the voltage can input to print out.
3.4.Use external power supply mode can extand to the large current measurement
4. Technology Specification
Function
Resistance Impedance
measurement Range
Resolution
Measurement Error
Anti-Power Frequency
50HZ
Voltage Interference
Ability
Test Current Wave
Internal Power Test
Current Frequency
Internal Power Maximum
Current Output
Internal Power Maximum
Voltage Output
Internal Power Test
Wires Demand
External Power Supply
Power Supply
Instrument Size
Instrument Weight
Data Storage
Measure the grounding impedance or resistance of the grounding
device, measure the on-off impedance or resistance between the
grounding devices, and measure the soil resistivity.
0Ω~200Ω
0.001Ω
±(Reading×2%+0.005Ω)
10V
Sine Wave
Auto 45Hz, 55Hz, double frequency, multiple frequency conversion
groups are available for optional use
5A
400V
Current wires copper core cross-sectional area≥2.0mm
Voltage wires copper core cross-sectional area≥1.5mm
0~50A(variable
frequency
transformer, constant current and constant voltage regulator
AC220V±10%,50Hz
440mm(L)×350mm(W)×210mm(H)
20KG
100 groups
2
large
current),
external
2
;
2
isolation

Publicidad