Identifying downstream loads from a breaker.
1)
Remove the panel cover and clamp around the hot wire of the energized (closed) circuit.
To maximize the signal, close the far end of the circuit by plugging in and turning
on a work light or other load into the furthest outlet; hence, making a complete
loop.
2)
Hang the battery pack onto the panel with the magnetic strap.
3)
Plug the clamp into the battery pack.
4)
Set the receiver to the highest sensitivity mode (
outlet while identifying all outlets and loads connected to the circuit. If the Receiver is
saturated, reduce the sensitivity range.
Weaker Signal - Open
Breaker
Energized
Stronger Signal - Closed
Breaker
Energized
Tracing Conduit.
1)
Clamp around the metallic conduit to be traced. If possible, ground the far end of the
conduit to close the loop. This can be created using the 25' lead and alligator clips to clip
onto the end of the conduit or electrical box with one clip and a remote neutral or water
pipe with the other alligator clip.
2)
Hang the battery pack onto the panel or conduit with the magnetic strap.
) and trace the circuit to the furthest
Light On
(Load)
Page 19
3)
Plug the clamp into the battery pack.
4)
Set the receiver to the highest sensitivity (
Receiver is saturated, reduce the sensitivity range.
Tracing industrial control circuits.
1)
Ensure that the circuit is energized (closed at the panel) at a minimum. To maximize the
signal, close the other end of the circuit by turning on a load, such as a motor or pump.
2)
Clamp around the hot wire of this energized (closed) circuit.
3)
Use the magnetic strap to hang the battery pack onto the panel or the motor control
cabinet.
4)
Plug the clamp into the battery pack.
5)
Set the receiver to the highest sensitivity (
end. If the receiver is saturated, reduce the sensitivity mode.
Battery Replacement
Transmitter:
Ensure that the test leads are removed from the input
jacks and the circuit under test.
1)
Remove the battery cap by loosening the screw.
2)
Replace batteries with (4) new AA batteries .
3)
Assemble cap and re-tighten the screw.
) mode and trace the conduit. If the