SinePower
10.2
Connecting the inverter to the battery
NOTICE!
A
Do not reverse the polarity. Reversing the polarity of the battery
connections will cause a great spark and the internal fuses will
melt. The fuses should only be replaced by an electrician!
NOTE
I
Tighten the nuts and bolts to a torque of 12 – 13 Nm. Loose con-
nections may cause overheating.
➤ Set the main switch (fig. 2 1, page 4) to "Off".
➤ Unscrew the four fastening screws (fig. 8 2, page 7) from the back side
of the device with the included hexagon socket wrench.
➤ Take off the hood (fig. 8 1, page 7).
➤ Guide the plus cable through the "POS (+)" opening and the minus cable
through the "NEG (–)" opening in the hood.
➤ Loosen the safety bolt slightly(fig. 8 3, page 7).
➤ Push the cable lug (fig. 8 5, page 7) of the positive cable between the
spring washer (fig. 8 4, page 7) and the positive terminal (fig. 8 6,
page 7).
➤ Screw the safety bolt back in.
➤ Connect the negative cable to the negative terminal (fig. 8 7, page 7).
➤ Connect the earth terminal (fig. 3 5, page 4) to the chassis with a cable
having a diameter of at least 16 mm².
➤ Replace the hood of the device and tighten the screws.
➤ Lay the positive cable from the inverter to the positive terminal of the ve-
hicle battery and connect it there.
➤ Lay the negative cable from the inverter to the negative terminal of the ve-
hicle battery and connect it there.
10.3
Connecting the 230 V power cable
➤ Connect the 230 Vw connection cable with safety coupling (fig. 1 3,
page 3) to the 230Vw output jack (fig. 3 3, page 4).
➤ Connect the safety plug to the 230 Vw mains