baltur BT 40 DSN 4T Manual De Instrucciones Para La Instalación, El Uso Y El Mantenimiento página 56

Quemadores de aceite combustible de dos etapas con bisagra
Ocultar thumbs Ver también para BT 40 DSN 4T:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ENGLISH
TABLE OF PIPELINE FOR BT 180 DSN - BT 250 DSN
WITH FUEL AT 5° AT 50° C (40° AT THE 5° C PUMPING TEMPERATURE)
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
GRAVITY FEED SYSTEM
Pump axis
Pump axis
SUCTION FEED SYSTEM
Pump axis
N.B. Comply with existing regulations regarding apparatus required in
the pipeline system
H - Height difference between minimum fuel tank level and pump axis.
L - Total length of pipeline, including vertical lenght. Subtract 0,25 mt.
0006080547_201610
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel
interception
device at burner shut off
9 One-way valve
10 Bottom valve
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
for every elbow or gate valve.
14 / 38
H
Total length meters
meters
Ø = 1" 1/2
Øi. 41 mm
1
35
35
1,5
40
40
2
50
50
2,5
50
50
H
Total length meters
meters
Ø = 1" 1/2
Øi. 41 mm
1
35
35
1,5
40
40
2
50
50
2,5
50
50
Dimension P = 3,5 m. (max.)
H
Total length meters
meters
Ø = 1" 1/2
Øi. 41 mm
0,5
25
25
1
20
20
1,5
15
15
2
10
10
2,5
5
5