DESCRIPTION OF TBG 45 / 60 OPERATION
E
N
When the main switch and the I/O switch (22) on the electrical
panel are closed, if the thermostats are closed, voltage will reach
G
the command and control device, which starts up the burner (led
19 comes on).
L
This turns on the fan motor for preventilation of the combustion
chamber.
I
The ignition transformer then comes on, and 2 seconds later the
gas valves open.
S
The main valve, which has two stages, has a device for adjusting
gas delivery for the first and second flame.
H
The safety valve is an ON/OFF valve.
Combustion air may be adjusted manually using the air lock (see
section entitled "Diagram for adjustment of air in single-stage burner
TBG 45-60").
As the burner is ON/OFF, the position of the air lock must be regu-
lated for operation at maximum capacity.
The presence of the flame, detected by the control device, permits
continuation and completion of ignition, turning off the ignition
transformer.
The second flame then comes on (the second stage in the main
valve opens).
If there is no flame, the appliance shuts down in "safety lock-out"
mode (led 20 comes on) within 3 seconds of the opening of the first
flame on the main valve.
In "safety lock-out" mode the valves are closed again immediately.
To release the appliance from safety lock-out mode, press button
(21) on the electrical panel.
Equipment or
programmer
LME 22.331A2
LME 22.233A2
Safety
Preventilation
time
time
ignition
s
s
3
30
3
30
DESCRIPTION OF TBG 45P - 60P OPERATION
When the main switch and the I/O switch (22) on the electrical
panel are closed, if the thermostats are closed, voltage will reach
the command and control device, which starts up the burner (led
19 comes on).
This turns on the fan motor for preventilation of the combustion
chamber. At the same time, the servomotor commanding the air
lock opens in the position corresponding to the second flame, so
preventilation takes place with the air lock in the second flame
position.
At the end of the preventilation phase, the air lock is returned to
the first flame position, then the ignition transformer comes on
and, 2 seconds later, the gas valves open.
The main valve, which has two stages, has a device for adjusting
gas delivery for the first and second flame.
The safety valve is an ON/OFF valve.
The air lock is operated by an electric servomotor(see 0002934711).
Keep in mind that when the burner is locked out because the ther-
mostat is tripped, the servomotor returns the air lock to the closed
position.
The presence of the flame, detected by the control device, permi-
ts continuation and completion of ignition, turning off the ignition
transformer. The second flame then comes on (combustion air is
increased and the second stage of the main valve opens).
If there is no flame, the appliance shuts down in "safety lock-out"
mode (led 20 comes on) within 3 seconds of the opening of the
first flame on the main valve.
In "safety lock-out" mode the valves are closed again immedia-
tely.
To release the appliance from safety lock-out mode, press button
(21) on the electrical panel..
Pre-
Post-
Opening time
ignition
1st flame valve
and the 2nd flame valve
s
s
2
2
2
2
10 / 18
00006081362_201106
time travel
opening
damper
s
s
11
12
11
30
time travel
closing
damper
s
12
30