86 P-band of control
(Xp)
87 Integral action time
of control (Tn)
Block "Boiler"
91
Boiler operating
mode
92
Maximum limitation
of boiler temperature
93
Minimum limitation
of boiler temperature
94
Switching differential
of boiler
95
Minimum limitation
of burner running
time
96
Release limit for
second burner stage
97
Reset limit for sec-
ond burner stage
98
Waiting time for
second burner stage
Block "Pump M1"
Operating mode
99
pump M1
Building Technologies
32.0 °C
(1.0...100.0)
°C
...................
120 s
(10...873)
......................
0
(0...2)
.........................
95 °C
(25...140)
°C
...................
10 °C
(5...140)
°C
...................
6 °C
(1...20)
°C
...................
4 min
(0...10)
min
................
50 °C×min
°C×min
(0...500)
..........
10 °C×min
°C×min
(0...500)
..........
20 min
(0...40)
min
................
1
(0...3)
.........................
74 319 0619 0 a
s
0 = with manual shutdown
(
key)
1 = with automatic shutdown
(OFF when there is no
demand for heat)
2 = without shutdown
No safety function
0 = circulating pump without
shutdown in the case of pro-
tective boiler startup
1 = circulating pump with shut-
down in the case of protec-
tive boiler startup
17.04.2008
en
51/288