133 Actuator opening
time
134 Actuator closing
time
135 P-band (Xp) d.h.w.
en
control
136 Integral action time
(Tn) d.h.w. control
Block "Derivative action time d.h.w. heating via heat exchanger"
137 Derivative action
time (Tv) d.h.w.
control
Block "Multifunctional relay"
141 Function of multi-
functional relay
Building Technologies
120 s
(10...873)
......................
120 s
(10...873)
......................
32.0 °C
(1.0...100.0)
°C
...................
120 s
(10...873)
......................
0 s
(0...255)
......................
0
(0...7)
.........................
74 319 0619 0 a
s
s
s
s
0 = no function
1 = outside temperature switch
(set operating lines
143...145)
2 = ON / OFF according to time
switch (select time switch
on operating line 146)
3 = relay ENERGIZED in the
case of fault
4 = relay ENERGIZED during
occupancy time
5 = relay ENERGIZED during
occupancy time incl. optimi-
zations
6 = relay ENERGIZED when
there is a demand for heat
7 = manually ON / OFF accord-
ing to operating line 142
If operating line 54 = 3, or oper-
ating line 125 is not 0, this op-
erating line cannot be changed
17.04.2008
56/288