Specifications; Measurement Categories - Greenlee FC-110 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Specifications

Overload Indication: Greater than 3V will be displayed on the AC voltage
measuring device
Low Battery Indication: Power Indicator flashes
Sensor Type: Rogowski Coil
Impact strength: The meter can be dropped from 1 meter's height
Clamp size: The FC-110 has a coil size of 25.4cm (10 inches). The FC-118 has a coil
size of 45.7cm (18 inches)
Electromagnetic field effect: When electromagnetic interference exists, the meter may
show an incorrect reading
Power Supply: 3 AAA 1.5V batteries
Environmental Limitations
Operating Environment: Indoor use
Maximum height: 2000m
Safety: IEC61010-1, IEC61010-031, IEC61010-2-032, CAT IV 600V
Pollution level: 2
Working temperature and humidity: 0° C- 30° C (≤ 80%RH), 30° C - 40° C (≤ 75%RH),
Storage temperature and humidity: -20%° C - 60° C (≤ 80%RH)

Measurement Categories

These definitions were derived from the international safety standard for insula-
tion coordination as it applies to measurement, control, and laboratory equipment.
These measurement categories are explained in more detail by the International
Electrotechnical Commission; refer to either of their publications: IEC 61010-1 or
IEC 60664.
Measurement Category II
Local level. Appliances, portable equipment, and the circuits they are plugged into.
Some examples include light fixtures, televisions, and long branch circuits.
Measurement Category III
Distribution level. Permanently installed machines and the circuits they are hard-wired
to. Some examples include conveyor systems and the main circuit breaker panels of a
building's electrical system.
Measurement Category IV
Primary supply level. Overhead lines and other cable systems. Some examples include
cables, meters, transformers, and other exterior equipment owned by the power utility.
40° C- 50° C (≤ 45%RH)
FC-110 • FC-118