Installation and Connection
3 INSTALLATION AND CONNECTION
3.1 MECHANICAL INSTALLATION
3.1.1 Environmental Conditions
Avoid:
Direct exposure to sunlight.
Inflammable, corrosive liquids or gases.
Metallic particles or oil mist.
Environmental conditions permitted for the operation of the inverter:
Ambient temperature surrounding the inverter: from 0 ºC (32 °F) until:
40 ºC (104 °F) - Nema4x/IP66 (mounted on the wall).
50 ºC (122 °F) - Nema4x/IP66 (mounted integrated on the motor).
40 ºC (104 °F) - Nema4x/IP66 mounted integrated on the motor (Refer to
130).
For temperatures surrounding the inverter higher than the specifications above, it is necessary
to apply a derating on the current of 2 % for each Celsius degree ( or 1.11 % each °F), limited
to an increase of 10 ºC (50 °F).
Air relative humidity: 5 % to 90 % non-condensing.
Maximum altitude: up to 1000 m (3.300 ft) - standard conditions (no derating required of
current).
From 1000 m to 4000 m (3.300 ft to 13.200 ft) current derating of 1 % each 100 m (or 0.3 %
each 100 ft) above 1000 m (3.300 ft) altitude.
From 2000 m to 4000 m (6.600 ft to 13.200 ft) maximum voltage reduction (480 V for 380...480 V
models) of 1.1 % for each 100 m (330 ft) above 2000 m (6.600 ft) altitude.
Pollution degree: 2 (according to EN50178 and UL508C), with non-conductive pollution.
Condensation must not originate conduction through the accumulated residues.
3.1.2 Positioning and Mounting
The external dimensions, the net weight (mass) of the inverter and the suggested torque values
are presented in
Figure B.1 on page 134
on page
128.
Integrate the motor
For assembling of the inverter coupled to the motor follow the step by step in
page 141
of
APPENDIX D - MOUNTING INSTRUCTIONS on page
8 | MW500
of
APPENDIX B - TECHNICAL SPECIFICATIONS
Table B.3 on page
Figure D.1 on
141.