Descargar Imprimir esta página

LU-VE ESB Instrucciones De Uso página 24

Publicidad

Code
Parameters
SET-POINT PARAMETERS
St1
Set point 1
St2
Set point 2
C00
Function mode
P01
St1 differential
P02
St2 differential
C03
Set-point type
ANALOG OUTLET PARAMETERS
C04
Outlet minimum value
C05
Outlet maximum value
C06
Soft-start
C07
Cut-off
C08
Speed-up
C09
Integrating action
C10
Outlet state with alarm sensor
INLET PARAMETERS
C13
Sensor type
C14
Refrigerant fluid type
C15
Minimum value
C16
Maximum value
C17
Inlet filter sensor
C18
Measurement unit
C19
Second sensor management
ALARM PARAMETERS
P25
Low threshold alarm level
P26
High threshold alarm level
P27
Alarm differential
P28
Alarm delay
DIGITAL I/O MANAGEMENT PARAMETERS
C29
Digital inlet 1
C30
Digital inlet 2
C31
Outlet relay management
MEASUREMENT MANAGEMENT PARAMETERS
C32
Unit display
C33
Value shown
P34
Effective measurement display
P35
Sensor 1 display
P36
Sensor 2 display
P37
Analog output % display
P38
Sensor 1 input % display
P39
Digital I/O state display
DEFROST MANAGEMENT PARAMETERS
P40
Defrost activation threshold
P41
Defrost disactivation threshold
P42
Defrost disactivation delay
P43
Maximum defrost duration
P44
Minimum defrost cycle
P45
Defrost output value
KEYBOARD/REMOTE CONTROL PARAMETERS
C50
Keyboard/remote control enabling
C51
Remote control enabling code
SERIAL CONNECTION MANAGEMENT PARAMETERS
C52
Serial connection type
C53
Serial address
C54
Baud-rate / Data dest. Address
C55
Frame
C56
Send reply delay
C57
Hardware board enabling
V out
10 V
0 V
-100 %
-8 °C
Differential 8 °C
E N G L I S H
REGULATION PARAMETERS FCM00NTC00 TEMPERATURE
Min.
Max.
Default
Note
0
100
40
Set to the relative temperature required - °C
0
100
40
Set to the relative temperature required - °CD
0
8
5
Dir. -St1 & Dir. -St2 (commanded by input ID1)
0,1
99,9
8
Differential in °C
0,1
99,9
8
Differential in °C
0
2
2
Set-point corrisponding to the maximum output value
0
C05
0
Minimum analog outlet value 0÷10 V expressed as %
C04
100
100
Maximum analog outlet value 0÷10 V expressed as %
0
120
2
Outlet variation speed to go from 0 to 100 % or viceversa
0
100
0
hreshold as a %, over which the outlet is disactivated
0
120
0
Threshold as a %, over which the outlet is forced to the maximum programmed value
0
999
0
Necessary value to maintain exact concordance with the set point
0
5
0
Outlet disactivated (0 %)
0
0
0
NTC sensor (10
0
7
0
Not accessible
-40
C16
0
Not accessible
C15
100
25
Not accessible
0
10
1
Not accessible
0
2
0
°C
0
4
1
The larger of the two sensors
-40
P26
-10
Low level alarm
P25
100
90
High level alarm
0
100
2
Defines the alarm reset lag
0
999
60
Alarm activation delay in seconds
0
5
0
Use for St1 / St2
0
5
0
Not active
0
8
1
Relay de-energised in presence of alarm
0
3
2
Always on
0
5
0
Effective measurement of the controlling sensor (See C19)
-
-
-
Display only
-
-
-
Display only
-
-
-
Display only
-
-
-
Display only
-
-
-
Display only
00.0
11.
-
Display only
0.0
P41
-
Not accessible
P40
100
100
Not accessible
0
240
5
Not accessible
1
60
1
Not accessible
1
240
1
Not accessible
0
100
0
Not accessible
0
4
4
Keyboard enabled, remote control enabled
0
99
0
Attributes a code to enable access to the remote control parameters
0
2
0
Connection disactivated
0
255
0
Not used
0
32
0
Not used
0
11
0
Not used
0
255
50
Not used
0
255
255
Not used
SET-POINT
Note parametri
DF
DL
DL/C = By the installer
0 %
0 °C
24
at 25 °C)
kOhm
= Default instrument
= By CAREL APPLICO
ESBT
Set
DL/C
L/C
DL
DL
DL
DL
DF
DF
DF
DF
DF
DF
DF
DL
DF
DF
DL
DF
DF
DL
DL
DL
DF
DL
DF
DF
DL
DF
DL
-
-
-
-
-
-
DF
DF
DF
DF
DF
DF
DF
DF
DF
DF
DF
DF
DF
DF

Publicidad

loading

Este manual también es adecuado para:

EsbpEsbtEsj