Operating manual
TSC5
The TSC5 control system is composed of a control unit (operating device), a circuit
board (Master), optional slave board as well as an Infrared-remote control.
Control unit (operating device)
1 Manual-Automatic switch (Auto/Man)
2 On-/Off-key heating
3 LED-display heating
4 Fan step-key (faster/slower)
5 LED-Display fan steps (Stop, 1, 2, 3, 4, 5)
6 LED-display thermo contact motors
7 LED-display frost protection
8 LED-display door contact
LED on:
LED off:
9 LED-display receiver for Infrared-remote control
10 RJ-45 connection to circuit board (Master)
11 DIP function selection switch SW1 (control unit-operating device)
SW1-1: Storage after power failure, On or Off
OFF:
After power failure the air curtain system is operated with the last
set fan and heating step
ON:
After power failure the air curtain system is not switched on,
Fan step 0 and the heating is switched off
SW1-2 +
SW1-3 After run time, for the automatic function
SW1-4: Basic loading operation, in automatic mode, with closed door
ON:
Fans off
OFF:
Fans on, Step 1
12 Terminal input room thermostat
Open:
Heating is switched off
Closed:
Heating is switched on
8
door is closed
door is open