6.4 Electrical protection

The power supply for the heat pump must come, preferably, from an exclusive circuit with regulatory
protection components (30mA differential protection) and a magneto-thermal switch.
- The electrical installation must be carried out by a specialized professional (electrician) in accordance with
the standards and regulations in force in the country of installation.
- The heat pump circuit must be connected to a safety earth circuit at the terminal block.
- The cables must be properly installed to prevent interference.
- The pump is intended for connection to a general power supply with earth connection.
- Section of the cable; This section is indicative and should be checked and adapted according to the needs
and conditions of use.
- The tolerance of acceptable voltage variation is +/- 10% during operation.
The connections must be dimensioned according to the power of the device and the state of
installation.
Models
ELYO SMART NN 06
ELYO SMART NN 09
ELYO SMART NN 12
ELYO SMART NN 16
ELYO SMART NN 20
ELYO SMART NN 25
ELYO SMART NN 25T
ELYO SMART NN 30
ELYO SMART NN 30T
These values are given as a guideline, only the intervention of an authorized technician
can determine the values corresponding to your installation.
The electric line must be equipped with a ground connection and with a circuit breaker with
difference 30mA in head.
6. Electrical Wiring
Circuit
breaker
2,5 mm²
7 A
84 m
10 A
57 m
13 A
43 m
16 A
34 m
20 A
29 m
26 A
135 m
9 A
105 m
34 A
21 m
13 A
-
Maximum length of the wire
4 mm²
135 m
90 m
68 m
54 m
45 m
210 m
160 m
34 m
27 m
- 28 -
6 mm²
10 mm²
200 m
335 m
130 m
225 m
100 m
170 m
80 m
135 m
66 m
110 m
315 m
525 m
240 m
400 m
49 m
84 m
39 m
68 m