6.2 Equipment overload and reassembly.
In case of an overload or short circuit the overload protection "BREAKER" will
switch to the "OFF" position, disconnecting the voltage output.
In case of overload, first unplug any plugged equipments.
Once the equipments are unplugged, assemble the overload protector again by rising the
protector to the "ON" position to restore the group voltage output.
• Graphic for single phase generators 230V:
• Graphic for 230/400V tri-phase generators:
If the overload protector trips again after connecting the devices, do not plug the
device. The plugged device may have a problem or exceeds the generator's power.
NOTE: Once you verify that the generator cannot support or accept the load,
please do not insist. Constant overloads may negatively affect the group.
Remember that many equipments need extra consumption for startup.
Equipments that use an engine such as compressors, water pumps, circular saws
or others consume up to 3 times more power for startup. For example, a 1000W
water pump will need 3000W to start up, therefore we would need a generator no
less than 3000W.
230V AC BREAKER
230V AC BREAKER
400V AC BREAKER
19