Indel B TB 30 AM DRAWER Instrucciones De Uso página 36

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 74
ENGLISH
TROUBLESHOOTING
All work on electrical parts or electrical connections and the refrigerant circuit must be carried out
by qualified and authorised personnel.
Warning: Disconnect electrical power before performing any operations on electrical parts or on
electrical connections.
Please also see the Display Errors Table at point 2.1.6.
Defect
The refrigerator does not
cool, the compressor will
not start.
The compressor only
performs brief attempts at
starting up.
The compressor functions
but doesn't cool.
The compressor runs for
a long time but doesn't
cool properly (reduced
efficiency).
36
Possible cause
No electrical power. Battery
in poor conditions. Faulty
thermostat. Defective
electronic control unit.
There is insufficient voltage or
else a drop in voltage during
the attempt to start. The
protection device is activated.
The Batteries are drained.
Loss of refrigerant through
the evaporator or the
tubing. Tubing clogged.
Insufficient ventilation,
the condensation unit is
overheating. The fan is not
working properly. There is too
much frost on the evaporator.
The door does not close
properly and lets in warm,
moist air. The condenser is
blocked by dust.
TB 30 AM DRAWER
Intervention
Check to make sure that the electronic
control unit is receiving sufficient power
and voltage; check the fuse. Verify that
the internal lighting is working and that
the compressor is receiving power.
Check the cables, lugs and connectors.
Verify that the battery is charging
properly. Check the thermostat: Bridge
T - C with a separate cable. If the
compressor will not start, its electronics
are probably defective. Replace. If the
compressor starts up with the bridge,
the thermostat is defective. Replace
the thermostat.
Check the cables and connections;
remove any traces of oxidation or
corrosion. Charge the batteries, start
the motor or connect the battery
charger.
Carry out a leak check and repair
any leaks, drain and refill the proper
amount of R134a refrigerant. (This
operation must be carried out by a
qualified technician.)
Increase the ventilation. Replace
the fan. Defrost the unit. Correct the
position of the door and check the
gasket. Clean the condensing unit.
TB30AM DRAWER_20-06-2018

Publicidad

Tabla de contenido
loading

Tabla de contenido