Defect
The circuit breaker
1. Unsuitable control voltage.
does not load the
springs electrically.
2. Defect in motorized drive.
1. Obstruction by the Off
Maneuver rod does
2. Obstruction by blocking of
not go in opening.
3. Poor positioning of circuit
1. Extraction rod is inserted.
2. Circuit breaker is not in
Impossible to extract
the circuit breaker.
3. Obstruction by blocking of
1. Circuit breaker and
Impossible to insert
2. Unsuitable positioning of
the circuit breaker.
3. Cutters blocked by
probable cause
button.
padlock.
breaker in extraction car.
disconnected position.
padlock.
extraction car are
incompatible as regards size.
lever.
padlock.
Corrective actions
1. Check control voltage.
2. Check motorized drive circuit.
3. Contact WEG.
1. Tighten Off button while inserting rod in
opening.
2. Remove padlock, releasing blocking.
3. Position circuit breaker correctly in
extraction car.
1. Remove extraction rod.
2. Place circuit breaker correctly in
disconnected position.
3. Remove padlock, releasing blocking.
1. Use compatible unit.
2. Reposition lever to right.
3. Remove padlock.