Preparing to Start the Pump
PREPARING TO START THE PUMP
Never run pump dry. Running pump with-
out water may cause pump to overheat, damaging seal
and possibly causing burns to persons handling pump.
Fill pump with water before starting.
Never run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding
persons handling pump.
1. Remove the priming plug from the priming tee and
fill the pump. Fill all piping between the pump and
the well and make sure that all piping in the well is
full. If you have also installed a priming tee in the
suction piping, remove the plug from the tee and fill
the suction piping.
2. Replace all fill plugs.
3. Power on! Start the pump. If you don't have water
after 2 or 3 minutes, stop the pump and remove the
fill plugs. Refill the pump and piping. You may have
to repeat this several times in order to get all the
trapped air out of the piping. A pump lifting water
25' may take as long as 15 minutes to prime.
4. After the pump has built up pressure in the system
and shut off, check the pressure switch operation by
opening a faucet or two and running enough water
out to bleed off pressure until the pump starts. The
pump should start when pressure drops to 30 PSI and
stop when pressure reaches 50 PSI. Run the pump
through one or two complete cycles to verify correct
operation. This will also help clean the system of dirt
and scale dislodged during installation.
Figure 10: Prime the Pump
Fill pump
and piping
through
priming tee.
2351 0396
NOZZLE CLEAN OUT
(LOW PRESSURE)
Use an icepick or brad awl to clean out the nozzle –
3/16" maximum diameter (see Figure 11). Be sure you
DO NOT enlarge the hole in the nozzle. Use PTFE pipe
thread sealant tape on plug when reassembling to seal it.
Figure 11: Use Icepick or Brad Awl to Clean Out Nozzle
Congratulations on a successful installation.
If you were unsuccessful, please refer to the
Troubleshooting section (Page 14).
10
1465 0497