Observe the following when using E.l.c.b:
•
Installation of E.l.c.b only between supplying mains and controller.
•
The E.l.c.b can be activated by:
- capacitive leakage currents between the cable screens during operation (especially with long,
screened motor cables)
- connecting several controllers to the mains at the same time
- RFI filters
3.2.3
Connection diagram
1/N/PE 180V 0%
264V + 0 %
48 Hz
62 Hz
L1
L2
L3
N
PE
L1
L2/N
0 2 Nm/2 b in
28 7
6 mm/0 24 in
< 1mm²/AWG 26 16
1k ...10k
7
8U
0 ... +5 V
0 ... +10 V
_
-10 ... +10 V
DANGER!
• Hazard of electrical shock! Circuit potentials are up to 480 VAC above earth ground.
Capacitors retain charge after power is removed. Disconnect power and wait until
the voltage between B+ and B- is 0 VDC before servicing the drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the
drive will result.
• Do not cycle mains power more than once every three minutes. Damage to the
drive will result.
2/PE 180V 0%
264V + 0 %
3/PE 180V 0%
48 Hz
62 Hz
L1
L1
L2
L2
L3
L3
N
N
PE
PE
L1
L2/N
COM
8U
9 A+ A1
20
20
E1 E2 E3
E4 A2
7
28 E1 E2 E3 E4
+
+12 V DC - 0 %
...
+30 V DC + 0 %
Installation
3/PE 320V 0 %
264V + 0 %
48 Hz
48 Hz
62 Hz
L1
L2
L3
N
PE
L1 L2
L3
COM
8I
7
62
71
72
PE
0 ... 20 mA
4 ... 20 mA
PE
ENGLISH
528V + 0 %
62 Hz
L1 L2
L3
0 5 Nm/4 5 lb in
6 mm/0 24 in
U V W
PES
PES
1 2 Nm/10 lb n
PES
9 mm/0 35 in
M
PES
3~
Tmd003
9