Installation and Connection
Use cables with the gauge indicated in
module.
Line
Current
(V)
(A)
380-480
380
500-690
250
It is recommended to use fuses when the braking module is connected to a DC link with more
than one inverter. Two fuses must be installed, one for the +UD and another for the -UD. The
current of each fuse must be 630 Arms with i
They must have an interruption capacity for direct voltage of 800 Vdc for the line 380...480 V,
1000 Vdc for the line 500...600 V and 1200 Vdc for the line 660...690 Vdc.
16 | DBW04
+UD
Braking resistor
Figure 3.4: Connections of the grounding and braking resistor
Table 3.1 on page 16
Table 3.1: Connecting cables of the DBW04
Minimum Section of
the Resistor Cables
[mm
(AWG)]
2
240 (2 x 4/0)
120 (4/0)
2
BR
to connect the DBW04 braking
Minimum Section of
the Cables for
+UD and -UD
[mm
(AWG)]
2
240 (2 x 4/0)
120 (4/0)
t maximum of 1.440.000 A
Minimum Section of
the Grounding Cable
[mm
(AWG)]
2
120 (4/0)
70 (2/0)
s.
2