Pipe water content
Internal Diameter
12 mm
14 mm
16 mm
Copper
20 mm
25 mm
32 mm
''12.7 mm (1/2'')''
''16.3 mm (5/8'')''
Steel
''21.7 mm (7/8'')''
''27.4 mm (11/16'')''
% Inhibited Ethylene
Glycol
Freezing temperature(*)
Capacity
Correction
Absorbed power
Factors
Loss of head
(*) NOTE: Temperature values are indicative.
Always refer to the temperatures indicated for the speciic product used
through the drain unit valve, Fig 9, item 3, and the system
drain, Fig 12/13, item 5.

6.1 - Recommended water diagram (Fig. 12/13)

Typical water circuit diagram for unit MCI__X
(see fig 12)
Typical water circuit diagram for unit MCI__H
(see fig 13)
Do not use the heat pump to treat industrial process,
swimming pool or sanitary water.
In all these cases, provide an intermediate heat exchanger.
20
RG66012647
Outer diameter
Liters / meter
14 mm
0.11 l/m
16 mm
0.15 l/m
18 mm
0.20 l/m
22 mm
0.31 l/m
28 mm
0.49 l/m
35 mm
0.80 l/m
3/8'' Gas
0.13 l/m
1/2'' Gas
0.21 l/m
3/4'' Gas
0.37 l/m
1' Gas
0.59 l/m
10%
20%
30%
40%
-4 °C
-9 °C
-15 °C
-23 °C
0.996
0.991
0.983
0.974
0.990
0.978
0.964
1.008
1,003
1,010
1,020
1,033
All copying, even partial, of this manual is strictly forbidden
Unit
Std
l/s
Nominal water flow
Min
l
Water content
system unit with
Max
l
expansion vessel
Max
kPa
Working pressure
Min
kPa
Filling pressure
Max
m
Diference in level
with unit at lowest
level
TABLE TO USE FOR CALCULATING
WATER CONTENT IN THE SYSTEM
Installed Unit
Unit content (*)
Pipe content (**)
Uses (fan-coil, panels, radiators, etc.) (***)
Total content (****)
(*) Consult the technical data table
(**) Consult the pipe water content table
(***) Consult the manual for the installed uses
(****) The water content of the system must be between the minimum and maximum
values for the units with hydronic kit and greater than the minimum value for units
without hydronic kit. The minimum value is necessary to provide optimal comfort.
For units without hydronic kit, add a suitable expansion vessel to the water content
of the system.
MCI
004_
006_
008_
012_
0.20
0.28
0.33
0.58
14
21
28
42
65
65
65
95
300
300
300
300
120
120
120
120
20
20
20
20
.............
l
.............
l
.............
l
.............
l
.............
015_
0.69
49
95
300
120
20