5. Commissioning, operation
Additional functions in normal operation to retrieve the recorded
Min/Max values
Using the
■
in the display for some seconds.
Using the
■
in the display for some seconds.
By simultaneously pressing the
■
values are deleted.
If the measuring range setting is changed, to maintain the measurement
accuracy, the display must be recalibrated.
5.3.3 Display information, overrange/underrange
Range:
Displayed range:
Usable range:
Advance warning of underrange: 3.6 ... < 3.9 mA
Advance warning of overrange: > 20.1 ... 21.5 mA
Underrange displayed:
Overrange displayed:
With the advance warning, the display blinks (normal display
■
alternates with horizontal bars).
For values under 3.6 mA, a horizontal bar alternates with the display
■
"undr".
For values over 21.5 mA, a horizontal bar alternates with the display
■
"over".
WIKA operating instructions model DIH10
button, the recorded value of the Max memory is shown
button, the recorded value of the Min memory is shown
and
buttons, the Min and Max
4 ... 20 mA
3.9 ... 20.1 mA
3.6 ... 21.5 mA
< 3.6 mA
> 21.5 mA
EN
17