6. Commissioning, operation

6. Commissioning, operation
CAUTION!
GB
Prior to commissioning, the pressure transmitter must be subjected to a visual inspection.
Only use the pressure transmitter if it is in perfect condition with respect to safety.

6.1 Mechanical mounting

The sealing faces at the instrument have to be undamaged and
clean.
When screwing the instrument in, the force required to do this must
not be applied through the casing, but only through the spanner flats
provided for this purpose and using a suitable tool.
The correct torque depends on the dimensions of the process
connection and the gasket used (form/material).
Do not exceed the following tightening torque:
max. 30 Nm
When screwing in, do not cross the threads.
For information on tapped holes and welding sockets, see Technical Information IN 00.14 at
www.wika.com.