2. Installation location
ZM200, 250
M200, 250
en
Fig. 2-4
4
(mm)
Fig. 2-3
A
Fig. 2-5
B
Fig. 2-6
2.3. Outline dimensions (Outdoor unit) (Fig. 2-3)
2.4. Ventilation and service space
2.4.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunction
may result.
The following shows three examples of precautions against strong winds.
1 Face the air outlet towards the nearest available wall about 50 cm away from the
wall. (Fig. 2-4)
2 Install an optional air guide if the unit is installed in a location where strong winds
from a typhoon, etc. may directly enter the air outlet. (Fig. 2-5)
A Air outlet guide
3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-6)
B Wind direction
2.4.2. When installing a single outdoor unit (Refer to the last page)
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
Refer to the figures for each case.
1 Obstacles at rear only (Fig. 2-7)
2 Obstacles at rear and above only (Fig. 2-8)
3 Obstacles at rear and sides only (Fig. 2-9)
4 Obstacles at front only (Fig. 2-10)
* When using an optional air outlet guide, the clearance is 500 mm or more.
5 Obstacles at front and rear only (Fig. 2-11)
* When using an optional air outlet guide, the clearance is 500 mm or more.
6 Obstacles at rear, sides, and above only (Fig. 2-12)
Do not install the optional air outlet guides for upward airflow.
2.4.3. When installing multiple outdoor units (Refer to the last page)
Leave 50 mm for ZM200, 250/M200, 250 space or more between the units.
1 Obstacles at rear only (Fig. 2-13)
2 Obstacles at rear and above only (Fig. 2-14)
No more than 3 units must be installed side by side. In addition, leave space as shown.
Do not install the optional air outlet guides for upward airflow.
3 Obstacles at front only (Fig. 2-15)
* When using an optional air outlet guide, the clearance is 1000 mm or more.
4 Obstacles at front and rear only (Fig. 2-16)
* When using an optional air outlet guide, the clearance is 1000 mm or more.
5 Single parallel unit arrangement (Fig. 2-17)
* When using an optional air outlet guide installed for upward airflow, the clearance is
1000 mm or more.
6 Multiple parallel unit arrangement (Fig. 2-18)
* When using an optional air outlet guide installed for upward airflow, the clearance is
1500 mm or more.
7 Stacked unit arrangement (Fig. 2-19)
The units can be stacked up to two units high.
No more than 2 stacked units must be installed side by side. In addition, leave space as
shown.