For the factory settings, please do the following steps:
Factory settings:
• Analogue output 4...20 mA or 0...10 V
• Binary output as Normally open
• Damping of the output with tier 2 (25 % LED)
Test function
The test function is used to check the correct connection of the probe to the control panel.
The analogue signal switches slowly between 4 mA and 20 mA. The LEDs (25% - 100 %) are on and off
one after the other.
Adjustment with EasyTeach-Button (ETF):
By releasing the EasyTeach-Button after approx.
20 seconds, the menu item adjustment „empty"
is activated
Adjustment with EasyTeach by Wire (ETW):
By breaking the EasyTeach connection after approx.
20 seconds, the menu item adjustment „empty" is
activated
The blue ring flashes with a double pulses
After the reset all previous adjustments are deleted.
A new adjustment is required.
Adjustment with EasyTeach-Button (ETF):
Pushing the EasyTeach-Button for more then 25
seconds activates the test function as long as you
release the EasyTeach-button.
Adjustment with EasyTeach by Wire (ETW):
By activating the EasyTeach connection for more
then 25 seconds, the test function is activated as
long as you disconnect the wire.
The blue ring flashes with a frequency of 0.5 Hz