Haier HSU18VHJ(DB) Manual De Instalación página 39

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Indoor uni t
4wire 14AWG
Control Wiring
HSU09VHJ(DB)-W
Power cable:
HSU12VHJ(DB)-W
Power cable:
HSU18VHJ(DB)-W
Power cable:
HSU24VHJ(DB)-W
Power cable:
All models: Control Wiring: 4wire, 14AWG
4wire 14AWG
Control Wiring
Indoor unit
HSU09XCK-W
Power cable:
Power cable:
HSU12XCK-W
3wire 14AWG
3wire 14AWG
Control Wiring
Indoor unit
HSU09XHK-W
Power cable:
3wire 14AWG
3wire 14AWG
Control Wiring
Indoor unit
HSU12XHK-W
Power cable:
1. If the fuse on PC board is broken please change it with the type of T.3.15A/250V
(indoor unit),25A/250V(outdoor unit).
2. The wiring method should be in line with the local wiring standard.
3. After installation, the power plug should be easily reached.
4. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch.
Outdoor unit
Power
cable
2wire with ground 12AWG
2wire with ground 12AWG
2wire with ground 12AWG
2wire with ground 12AWG
Outdoor unit
2wire with ground 12AWG
2wire with ground 12AWG
Grounding Line
Outdoor unit
2wire with ground 12AWG
Grounding Line
Outdoor unit
2wire with ground 12AWG
Outdoor unit
Installation of Outdoor Unit
Drawing for the installation of indoor and outdoor units
Install according to
Connection of pipes
To bend a pipe, be careful not to crush the pipe,
and the bending radius should be 30 (1 1/6) to 40 mm (1 4/7) or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Half union
Flare nut
Pipe Diameter(ǿ)
Liquid side6.35mm(1/4")
Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs
Gas side 12.7mm(1/2")
Spanner
Torque wrench
Gas side 15.88mm(5/8")
Ensure that no dirt or debris enters the pipe.
The standard pipe length is 7m (27 9/16) . If it is over 7m (27 9/16) , the function
of the unit will be affected. If the pipe has to be lengthened, the refrigerant should
be charged, according to 20 g/m (0.018 oz/inch). But the charge of refrigerant must
be conducted by professional air conditioner servicer. Before adding additional
refrigerant, perform air purging from the refrigerant pipes and indoor unit using
a vacuum pump,then
charge additional refrigerant.
CAUTION
Indoor unit
B
A
Outdoor unit
Outdoor unit
Oil trap
B
Indoor unit
A
Connection
Take off the panel(top), by removing the 5 screws.
Remove the plugs on the conduit plate.
Temporarily mount the conduit tubes on the conduit plate.
Connect both the power supply and unit wire harness to
the corresponding terminals on the terminal board.
Ground the unit in accordance with local codes.
Allow several extra inches of wire for making wiring connections.
Use lock nuts to secure conduit tubes.
Attaching Drain-Elbow
If the drain-elbow is used,
please attach it as figure. (Note:
Only for heat pump unit.)
Fastening torque
18N.m/13.3Ft.lbs
55N.m/40.6Ft.lbs
60 N.m/44.3Ft.lbs
Outdoor unit
B
Indoor unit
A
Max.Elevation: Amax=1 m
In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7m
Max. Length: Bmax=15m
In case the pipe length B is
more than 10m, the refrigerant
should be charged, according
to 20 g/m.
3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hsu12vhj

Tabla de contenido