5. CONFIGURATION

Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.

5.1 Standard settings: ready for use

On delivery, the Phoenix Inverter is set to standard factory values. In general, these
settings are suitable fo stand-alone operation.
Standard factory settings
Inverter frequency
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Programmable relay

5.2 Explanation of settings

Settings that are not self-explanatory are described briefly below. For further
information, please refer to the help files in the software configuration programs (see
Section 5.3).
Inverter frequency
Output frequency
Adjustability: 50Hz; 60Hz
Inverter voltage
Output voltage of the Inverter.
Adjustability: 210 – 245V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
increase total inverter power (several devices in parallel)
create a 3-phase system.
To this end, the devices must be mutually connected with RJ45 UTP cables.
Standard device settings, however, are such that each device operates in stand-alone
operation. Reconfiguration of the devices is therefore required.
AES (Automatic Economy Switch)
If this setting is turned 'on', the power consumption in no-load operation and with low
loads is decreased by approx. 20%, by slightly 'narrowing' the sinusoidal voltage.
The AES Mode can be set with a DIP switch.
Applicable in stand-alone configuration only.
50 Hz
230 VAC
stand-alone
off
alarm function