- Press the "CONFIRM" button. The unit will automatically start the air flow rate.
While the automatic airflow setting mode
Confirm
is active, it will turn "ON" on the remote
control.
After 3 or 6 minutes, the unit will stop automatically following the completion of the automatic adjustment mode.
5.
WARNING:
- Never modify the gates or grilles while the automatic airflow adjustment mode is active.
- If there is no change in the air vents after the automatic adjustment, be sure to restore the automatic airflow adjustment.
- If there is no change in the ventilation channels after the automatic adjustment, contact your supplier, especially if this happens after
testing the outdoor unit or if the unit has been moved from one place to another.
- Do not perform automatic adjustment of airflow if fans, air treatment units or air drawers are installed in the same duct as the air
conditioner.
- If the duct has been modified, you must reset the duct by performing a new adjustment from point 3.