Room Temperature - Honeywell C7189U Instrucciones De Instalación

Ocultar thumbs Ver también para C7189U:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

C7189U REMOTE INDOOR SENSOR
CHECKOUT
For best results, allow the sensor to absorb the air
moving through the room for a minimum of twenty
minutes before taking a resistance measurement.
1. Use an accurate thermometer (+/-1ºF[0.5ºC])
measure the temperature at the sensor location.
2. Remove one wire from one of the sensor's wiring
terminals. Use an ohmmeter to measure the
resistance across the sensor. Verify the sensor
accuracy with the temperature/resistance in
Table 1.
CALIBRATION
The sensor is calibrated at the factory and cannot be
recalibrated in the field.
Home and Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
Table 1. Sensor Resistance at Room Temperature.

Room Temperature

°F
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
® U.S. Registered Trademark
© 2018 Honeywell International Inc.
69-1710EFS—02 M.S. Rev. 08-18
Printed in United States
Ohms of
°C
Resistance
4.4
22537
5.6
21516
6.7
20546
7.8
19626
8.9
18754
10.0
17926
11.1
17136
12.2
16387
13.3
15675
14.4
14999
15.6
14356
16.7
13743
17.8
13161
18.9
12607
20.0
12081
21.1
11578
22.2
11100
23.3
10644
24.4
10210
25.6
9795
26.7
9398
27.8
9020
28.9
8659
30.0
8315
31.1
7986
32.2
7672
33.3
7372
34.4
7086
35.6
6813
36.7
6551
37.8
6301

Publicidad

Tabla de contenido
loading

Tabla de contenido