Troubleshooting; Recovery Problems; No Display When Main Power Switch Is On; Refilling Does Not Flow - Viper VR-6000 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTRUCTIONS MANUAL

TROUBLESHOOTING

RECOVERY PROBLEMS

Problem: "HIGH-PRESSURE" LED
Solution:
Be sure tank valves are open and hoses are properly connected to the tank. Check for the
presence of air in the storage tank (see air purge), if necessary purge as required.
After a HIGH PRESSURE shutdown it will be necessary to remove the back plastic cover and
manually reset the high pressure switch bypressing on the small red button on the top of the
pressure switch located on the top of the manifold.
Problem: "SERVICE" message
Solution:
Remove and replace the low side filter/dryer. See REPLACING THE FILTER/DRYER
Problem: When in RECOVERY displayshows error n°1 (ER 01)
Solution:
The A/C system is empty, run EVACUATE
Problem: When in EVACUATE the displayshows error n°2 (ER 02)
Solution:
The A/C system isn't empty, run RECOVERY

NO DISPLAY WHEN MAIN POWER SWITCH IS ON

Problem: Blown main fuse
Solution:
Replace fuse 15A, located in the input power connector. A spare fuse is included in the
machine.

REFILLING DOES NOT FLOW

Problem: Refrigerant supplyempty or low
Solution:
Add refrigerant to the tank, check the scale calibration.
Problem: Pressure of the A/C system equals the pressure of the bottle
Solution:
Close the high side tap, turn on the A/C system, let the compressor of the A/C system
recover the remaining refrigerant.
Problem: Tank valves closed.
Solution:
Open liquid (RED) valve and be sure hose is properly connected to the tank and the unit.
24