English
IN THE EVENT OF A MALFUNCTION OR BREAKDOWN,
grounding provides a path of least resistance for electric
current and reduces the risk of electric shock. This tool is
equipped with an electric cord that has an equipment-
grounding conductor and a grounding plug. The plug
MUST be plugged into a matching receptacle that is
properly installed and grounded in accordance with ALL
local codes and ordinances.
DO NOT MODIFY THE PLUG PROVIDED. If it will not fit the
receptacle, have the proper receptacle installed by a
qualified electrician.
IMPROPER CONNECTION of the equipment-grounding
conductor can result in risk of electric shock. The
conductor with green insulation (with or without yellow
stripes) is the equipment-grounding conductor. If repair or
replacement of the electric cord or plug is necessary, DO
NOT connect the equipment-grounding conductor to a live
terminal.
CHECK with a qualified electrician or service person if you
do not completely understand the grounding instructions,
or if you are not sure the tool is properly grounded.
USE ONLY 3-wire extension cords that have 3-prong
grounding plugs and 3-pole receptacles that accept the
tool's plug. Repair or replace damaged or worn cord
immediately.
Use a separate electrical circuit for your tools. This circuit
must not be less than # 12 wire and should be protected
with a 15 Amp time delay fuse. Before connecting the
motor to the power line, make sure the switch is in the
OFF position and the electric current is rated the same as
the current stamped on the motor nameplate. Running at
a lower voltage will damage the motor.
This tool is intended for use on a circuit that has a
receptacle like the one illustrated in Figure A.
shows a 3-prong electrical plug and receptacle that has a
grounding conductor. If a properly grounded receptacle is
not available, an adapter (Figure B) can be used to
temporarily connect this plug to a 2-contact ungrounded
receptacle. The adapter (Figure B) has a rigid lug extending
from it that MUST be connected to a permanent earth
ground, such as a properly grounded receptacle box.
THE TENPORARY ADAPTER SHOULD BE USED ONLY
UNTIL A PROPER GROUNDED PUTLET CAN BE
INSTALLED BY A QUALIFIED ELECTRICIAN. The Canadian
Electrical Code prohibits the use of adapters.
CAUTION: In all cases, make certain the receptacle is
properly grounded. If you are not sure, have a qualified
electrician check the receptacle.
WARNING
This tool is for indoor use only. Do not expose to rain or
use in damp locations.
Fig. A
Fig. B
Grounding Lug
This band saw is for indoor use only. Do not expose to
rain or use in damp locations
GUIDELINES FOR EXTENSION CORDS
USE PROPER EXTENSION CORD. Make sure your
extension cord is in good condition. When using an
extension cord, be sure to use one heavy enough to carry
the current your product will draw. An undersized cord
will cause a drop in line voltage, resulting in loss of power
and cause overheating. The table below shows the correct
size to use depending on cord length and nameplate
ampere rating. If in doubt, use the next heavier gauge.
The smaller the gauge number the heavier the cord.
Be sure your extension cord is properly wired and in good
condition. Always replace a damaged extension cord or
have it repaired by a qualified person before using it.
Protect your extension cords from sharp objects,
excessive heat and damp or wet areas.
MINIMUM GAUGE FOR EXTENSION CORDS (AWG)
(When using 120 Volt only)
Ampere Rating
Not
More Than More Than
0
6
6
10
10
12
12
16
— 6 —
3-Prong Plug
Grounding Prong
Properly Grounded
3-Prong Receptacle
Make Sure This
is Connected to a
Known Ground
2-Prong
Receptacle
Adapter
WARNING
Total length in feet
25'
50'
100'
18
16
16
18
16
14
16
16
14
Not Applicable
14
12
150'
14
12
12