Function
Function
Setting number Default
number
00
Start/Stop
External
Emergency
46
01
control
stop
02 Forced stop
00
All
Error
Display only
report
47
on central
target
01
remote
controller
Follow the
Fan set-
setting on
00
ting when
the remote
cooling
49
controller
thermo-
stat OFF
01
Stop
6.4.1. Button name and function
TIMER indicator lamp (Orange)
OPERATION indicator lamp (Green)
6.4.2. Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION indicator
ON
lamp (Green)
OFF
ON
TIMER indicator
0.5s 0.5s 0.5s 0.5s
lamp (Orange)
OFF
ON
FILTER indicator
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
lamp (Red)
OFF
9377773098-01_IM.indb 10
9377773098-01_IM.indb 10
Details
○
Allow an external controller to start or
stop the system, or to perform an emer-
gency stop.
* If an emergency stop is performed from
an external controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor unit stops by
the input to the external input terminals,
and Start/Stop by a remote controller is
restricted.
○
Change the target for reporting errors.
Errors can either be reported in all loca-
tions, or only on the wired remote.
When set to 01, the fan stops when the
○
thermostat is OFF in cooling operation.
Connection of the wired remote control-
ler (2-wire type or 3-wire type) and
switching its thermistor are necessary.
FILTER indicator lamp (Red)
Indication pattern
Indoor unit address
Refrigerant address
ON
Flash (1.0s ON/1.0s OFF)
Address: tens place (0.5s ON/0.5s OFF)
Address: ones place (0.5s ON/0.5s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator lamp
1.0s
1.0s
(Green)
OFF
TIMER indicator
ON
lamp (Orange)
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
OFF
ON
FILTER indicator
lamp (Red)
OFF
• Setting details
Function number
Item
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "6.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
Function number; tens place (0.5s ON/0.5s OFF)
Function number; ones place
TIMER indicator lamp (Orange)
(0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
(Example) Function : 31, Setting number : 2
OPERATION
ON
indicator lamp
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
(Green)
OFF
ON
TIMER indicator
lamp (Orange)
0.5s 0.5s
OFF
ON
FILTER indicator
0.5s
0.5s
0.5s
0.5s
lamp (Red)
OFF
6.5. Connecting the wired remote controller
(If necessary)
In order to connect the wired/simple remote controller to the external switch controller, the
wire assembly (Accessories) which is attached to the indoor unit needs be connected to the
end of remote controller cable.
(1) Use a tool to cut off the terminal on the end of the remote controller cable, and then
remove the insulation from the cut end of the cable.
For 2-wire type
20 mm
(2) Connect the remote controller cable with connecting cable with solder. IMPORTANT:
Be sure to insulate the connection between the cables.
For 2-wire type
Solder and insulate the connected parts.
Remote controller
cable (non polar)
Cut and insulate
For 3-wire type
Solder and insulate the connected parts.
White
Red
Black
Remote controller
cable
For dual control or group control
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Setting number
00 to 63
00 to 99
Indication pattern
1 cycle 12 sec
9 sec
11 sec
10 sec
20 mm
For 3-wire type
Red
White
Black
Connecting cable
(Accessories)
Red
White
Black
Connecting cable
(Accessories)
En-10