Extended Parameters - SODECA VSD1/A-RFM-0.5 Manual De Instalación Y Operación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

P-12
Primary Command Source
0: Terminal Control. The drive responds directly to signals applied to the control terminals.
1: Uni-directional Keypad Control. The drive can be controlled in the forward direction only using an external or remote Keypad
2: Bi-directional Keypad Control. The drive can be controlled in the forward and reverse directions using an external or remote Keypad.
Pressing the keypad START button toggles between forward and reverse.
3: Modbus Network Control. Control via Modbus RTU (RS485) using the internal Accel / Decel ramps
4 : Modbus Network Control. Control via Modbus RTU (RS485) interface with Accel / Decel ramps updated via Modbus
5 : PI Control. User PI control with external feedback signal
6 : PI Analog Summation Control. PI control with external feedback signal and summation with analog input 1
7 : CAN open Control. Control via CAN (RS485) using the internal Accel / Decel ramps
8 : CAN open Control. Control via CAN (RS485) interface with Accel / Decel ramps updated via CAN
9 : Slave Mode. Control via a connected from manufacturer drive in Master Mode. Slave drive address must be > 1.
NOTE
When P-12 = 1, 2, 3, 4, 7, 8 or 9, an enable signal must still be provided at the control terminals, digital input 1
P-13
Operating Mode Select
Provides a quick set up to configure key parameters according to the intended application of the drive. Parameters are preset
according to the table.
0 : Industrial Mode. Intended for general purpose applications.
1: Pump Mode. Intended for centrifugal pump applications.
2 : Fan Mode. Intended for Fan applications.
Setting
Application
0
1
2
P-14
Extended Menu Access code
Enables access to Extended and Advanced Parameter Groups. This parameter must be set to the value programmed in P-37 (default:
101) to view and adjust Extended Parameters and value of P-37 + 100 to view and adjust Advanced Parameters. The code may be
changed by the user in P-37 if desired.

6.2. Extended Parameters

Par.
Description
P-15
Digital Input Function Select
Defines the function of the digital inputs depending on the control mode setting in P-12. See section 7 Analog and Digital Input
Macro Configurations for more information.
P-16
Analog Input 1 Signal Format
 = 0 to 10 Volt Signal (Uni-polar). The drive will remain at 0.0Hz if the analog reference after scaling and offset are applied is
=<0.0%
 = 0 to 10 Volt Signal, bi-directional operation. The drive will operate the motor in the reverse direction of rotation if the
analog reference after scaling and offset are applied is <0.0%. E.g. for bidirectional control from a 0 – 10 volt signal, set P-35 =
200.0%, P-39 = 50.0%
 = 0 to 20mA Signal
 = 4 to 20mA Signal, the VSD will trip and show the fault code  if the signal level falls below 3mA
 = 4 to 20mA Signal, the VSD will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
 = 20 to 4mA Signal, the VSD will trip and show the fault code  if the signal level falls below 3mA
 = 20 to 4mA Signal, the VSD will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
 = 10 to 0 Volt Signal (Uni-polar). The drive will operate at Maximum Frequency / Speed if the analog reference after scaling
and offset are applied is =<0.0%
P-17
Maximum Effective Switching Frequency
Sets maximum effective switching frequency of the drive. If "rEd" is displayed, the switching frequency has been reduced to the level in P00-
32 due to excessive drive heatsink temperature.
P-18
Output Relay Function Select
Selects the function assigned to the relay output. The relay has two output terminals, Logic 1 indicates the relay is active, and
therefore terminals 10 and 11 will be connected.
0 : Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3 : Drive Tripped. Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit. Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit. Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit. Logic 1 when the motor current is below the adjustable limit set in P-19
8 : Analog Input 2 > Limit. Logic 1 when the signal applied to analog input 2 exceeds the adjustable limit set in P-19
9 : Drive Ready to Run. Logic 1 when the drive is ready to run, no trip present.
P-19
Relay Threshold Level
Adjustable threshold level used in conjunction with settings 4 to 7 of P-18
P-20
Preset Frequency / Speed 1
P-21
Preset Frequency / Speed 2
P-22
Preset Frequency / Speed 3
Current Limit (P-54)
General
150%
Pump
110%
Fan
110%
0
9
0
2
Torque Characteristic (P-28 & P-29)
Constant
Variable
Variable
0
65535
Minimum
Maximum
0
17
See Below
4
32
0
9
0.0
200.0
-P-01
P-01
-P-01
P-01
-P-01
P-01
17
0
1
0
0
Spin Start (P-33)
0 : Off
0 : Off
2 : On
0
0
VSD*/A
VSD*/B
Default
Default
0
0
U0-10
U0-10
8 (HV/LV)
8 (HV/LV)
1
1
100.0
100.0
5.0
5.0
Hz / RPM
25.0
25.0
Hz / RPM
40.0
40.0
Hz / RPM
-
-
-
Units
-
-
kHz
-
%