Descargar Imprimir esta página

Velleman HAMGSM133 Manual Del Usuario página 10

Módulo de mando a distancia bidireccional móvil 2 i/2 o
Ocultar thumbs Ver también para HAMGSM133:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Request logic alarm level
Command:
LIV?
Example:
LIV?
Get a list of logic alarm levels on both inputs.
Inhibition time input 1
Command:
INI1:mm
Example:
INI1:02
After alarm activation, the device will not check the alarm level on input 1 for 2 minutes
(inhibition time).
Default = 5 minutes
Inhibition time input 2
Command:
INI2:mm
Example:
INI2:15
After alarm activation, the device will not check the alarm level on input 2 for 15 minutes
(inhibition time).
Default = 5 minutes
Request inhibition times
Command:
INI?
Example:
INI?
Get a list of the inhibition time on both inputs.
Reset inhibition time input 1
Command:
TIZ1x
Example:
TIZ11
Inhibition time reset on input 1 when input 1 is idle.
Default = no reset
Reset inhibition time input 2
Command:
TIZ2x
Example:
TIZ20
Inhibition time does not reset on input 2 when input 2 is idle.
Default = no reset
Request status of reset function
Command:
INI?
Example:
INI?
Receive the status of the reset function on the inputs.
Alarm condition time-out input 1
Command:
OSS1:ss
Example:
OSS:08
The alarm on input 1 must remain for 8 seconds before the alarm is passed on.
Default = 1 second
Alarm condition time-out input 2
Command:
OSS2:ss
Example:
OSS2:15
The alarm on input 2 must remain for 15 seconds before the alarm is passed on.
Default = 1 second
15/12/2011
mm = time in minutes (00~59)
mm = time in minutes (00~59)
x = 0 (no reset) or 1 (reset)
x = 0 (no reset) or 1 (reset)
ss = time in seconds (00~59)
ss = time in seconds (00~59)
HAMGSM133
10
© Velleman nv

Publicidad

loading