Knowyour System Control Panel - Briggs & Stratton 190839GS Manual Del Propietário

Ocultar thumbs Ver también para 190839GS:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Briggs &Stratton P ower Products Home Generator System
Owners
Manual
Com_ b./Eo_*_ Cu_ H, omn_
KNOWYOUR
SYSTEM CONTROL
PANEL
Compare this Control Panel illustration with your generator to familiarize yourself with the location of these important
contro]s:
Circuit
Breaker
Hour Meter
15 Amp
__-------
Fuse
Set Exercise
Switch
Diagnostic
LED
AUTO/OFF/MANUAL
Switch
15 Amp Fuse -- Protects the Home Generator System
DC control circuits. If the fuse has 'blown' (melted open)
or was removed, the engine cannot crank or star_ Replace
the fuse using only an identical BUS AGC 15A fuse.
AUTO/OFF/MANUAL
Switch --This
three-position
device is the most important control on the system and is
used as follows:
• "AUTO"
position is the normal operating position. If a
utility power outage is sensed, the system will start the
generator, let it reach stable operating speed, then
connect generator power to the transfer switch.When
utility power is restored, the system reconnects utility
power to the transfer switch, lets the engine stabilize
internal temperatures, shuts off the generator, and waits
for the next utility power outage.While waiting, it
maintains battery with trickle charge.
• "OFF"
position turns off running generator, takes system
out of Automatic
mode and resets any detected faults.
• "MANUAL"
position starts the engine but does not
disconnect the transfer switch from utility power. It is
used for maintenance or diagnostic functions.
Circuit
Breaker --
Protects the system from shorts and
other over-current conditions. Must be ON to supply
power to the Automatic Transfer Switch.
Diagnostic
LED -- Used for troubleshooting
operational
problems with the Home Generator System.All fault
conditions are described in the section "Fault Detection
System".
Hour
Meter
--The
hour meter records
the total
number
of hours the generator
has been running and is used to
schedule maintenance
tasks.
Set Exercise Switch -- Used to set the exercise cycle
start time and day-of-the-week. Exercise cycle only occurs
in AUTO mode.
II