no. of
Fault Description
service lED
Blinks
17
Power to the wireless
adapter overloaded.
18
Wireless
communication
from wireless
adapter failed.
Cleaning
Tank was slow to
Required
drain during last
light
automatic flush cycle
is on.
or 12-month cleaning
interval time
has expired.
TrueSTEAM Humidification System 69-2285EFS—05
Auto-recoverable?
steps to Fix
(Performed only By Professional HVAC technician)
Yes, system will
1.
Verify wiring between TrueSTEAM and the wireless adapter.
return to "Ready"
2.
Ensure DIP switches are set correctly. (DIP 3 up. Also DIP 4 up
if fault no longer
if TrueSTEAM R and C aren't wired.)
exists in one hour.
3.
If the fault persists, replace the wireless adapter.
Yes, system will
1.
Verify wiring between TrueSTEAM and the wireless adapter.
return to "Ready"
2.
Verify the Prestige control is operating correctly.
after one minute.
3.
If the fault persists, replace wireless adapter and re-enroll
connection to Prestige.
N/A
Follow the tank cleaning steps. See "Manual Cleaning Cycle"
on page 24.
33