Sends/Executes Control Operations:
•
Maximum number of CROB (obj. 12, var. 1) objects supported in a single message
1
•
Maximum number of Analog Output (obj. 41, any var.) supported in a single message
0
Pattern Control Block and Pattern Mask (obj. 12, var. 2 and 3 respectively)
supported.
CROB (obj. 12) and Analog Output (obj. 41) permitted together in a single message.
WRITE Binary Outputs
SELECT (3) / OPERATE (4)
DIRECT OPERATE (5)
DIRECT OPERATE - NO ACK (6)
Count > 1
Pulse On
Pulse Off
Latch On
Latch Off
Queue
Clear Queue
_______________________________________________________________________
Attach explanation:
•
All points support the same Function Codes: (3) Select, (4) Operate, (5)
Direct Operate and (6) Direct Operate - No ACK.
•
Maximum Select/Operate Delay Time: 60 seconds.
•
Count can be >1 only for PULSE ON and PULSE OFF
Atención
© ZIV Aplicaciones y Tecnología, S.A. Zamudio 2004
Este documento contiene información confidencial propiedad de ZIV S.A. Cualquier forma de reproducción o
divulgación está absolutamente prohibida y puede ser causa de severas medidas legales.
DNP 3.0 : Device Profiles Document
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
Never
Always
26 of 84
Page
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable