Descargar Imprimir esta página

ZIV 6MCV Manual De Instrucciones página 235

Publicidad

OBJECT
Obj Var
60
1
Class 0 Data
60
2
Class 1 Data
60
3
Class 2 Data
60
4
Class 3 Data
80
1
Internal Indications
--
--
No Object (Cold Start)
--
--
No Object (Warm Start)
--
--
No Object (Delay Measurement)
NOTES
C:
Device supports write operations on Time and Date objects. Time Synchronization-Required Internal Indication bit (IIN1-
4) will be cleared on the response.
D:
The device can be configured to send or not, unsolicited responses depending on a configuration option by means of
MMI (Man-Machine Interface or front-panel user interface ZIVercomPlus). Then, the Master can Enable or Disable
Unsolicited messages (for Classes 1, 2 and 3) by means of requests (FC 20 and 21).
If the unsolicited response mode is configured "on", then upon device restart, the device will transmit an initial Null
unsolicited response, requesting an application layer confirmation. While waiting for that application layer confirmation,
the device will respond to all function requests, including READ requests.
E:
Restart Internal Indication bit (IIN1-7) can be cleared explicitly by the master.
F:
The outstation, upon receiving a Cold or Warm Start request, will respond sending a Time Delay Fine object message
(which specifies a time interval until the outstation will be ready for further communications), restarting the DNP process,
clearing events stored in its local buffers and setting IIN1-7 bit (Device Restart).
G:
Device supports Delay Measurement requests (FC = 23). It responds with the Time Delay Fine object (52-2). This object
states the number of milliseconds elapsed between Outstation receiving the first bit of the first byte of the request and the
time of transmission of the first bit of the first byte of the response.
Atención
© ZIV Aplicaciones y Tecnología, S.A. Zamudio 2004
Este documento contiene información confidencial propiedad de ZIV S.A. Cualquier forma de reproducción o
divulgación está absolutamente prohibida y puede ser causa de severas medidas legales.
Description
Page
DNP 3.0 : Device Profiles Document
REQUEST
(MCV parse)
Func
Qual
Codes
Codes
(dec)
(hex)
1
6
1
6,7,8
20,21
6
1
6,7,8
20,21
6
1
6,7,8
20,21
6
0
2
index=7
13
14
23
72 of 84
RESPONSE
(MCV respond)
Func
Qual
Codes
Codes
Notes
(dec)
(hex)
129
1
129,130
28
D
129,130
28
D
129,130
28
D
E
F
F
G

Publicidad