DUCT INSTALLATION
Ductable outlet air connections
CHD – cassette units have primary air flow connection.
They are equipped with inlets for treated air on the corner of
the unit. This air is mixed with the untreated room air inside
the appliance.
The size and the location of the outlets is shown by the
drawings.
All air ducting departing from the fan-coil unit must fea-
ture thermal insulation to avoid condensation and drip-
ping water.
After duct insulation, complete the water and electrical
connections.
1
Branch Duct Dimension (mm)
2
(All dimensions shown in mm)
Branch duct flange
(optional)
Branch Duct Connection
• The side opening allows separate ductwork to be installed
for branch ducting. (Figure 1 and Figure 2).
• Cut and remove anti-condensate insulating material.
• Install your flanges and conduits to casing. Conduit can be
flexible polyester with spring core or corrugated aluminum
externally coated (dia.4 in.) with anti-condensate material
(fiberglass 12-25 mm thickness).
Order flanges (spigots) and blanking plates as accessories
separately.
Fresh air flange
Branch duct flange (optional)
(optional)
Installation
Fresh air flange
(optional)
17
EN